Forney supplies a complete scope of equipment with each duct burner system.
Typical Scope:
Horizontal (or vertical) Burner Elements
Integral Flow Bafes
ANSI B31.1 Fuel Skid
Burner Management System
Redundant Scanner Cooling Air Blowers
MAXFire® Igniter with HESI
Flame Scanner
Optional Scope:
Pressure Reducing Station
Fuel Flow Measurement
CFD
Individual Element Isolation
Interconnecting Piping
ANSI B31.3 Fuel Skid
Application Specications
Duct cross sections: 3 to 50 feet
Heat inputs: 10 to 1100 MMBtu/hr
Inlet oxygen levels: ≥ 10.5% wet without augmenting air
Inlet H
2
O: ≤ 20% without augmenting air
TEG distribution to the burner: ± 20% of the average velocity over 90% of the cross section
Typical Emissions
For most advanced gas turbine applications ring natural gas (assuming < 12% wet H
2
O; Firing Temperatures
>1200°F), we offer the following emission guarantees over turndown - without augmenting air:
Non-Power Augmentation*
(lb/MMBtu, HHV)
Power Augmentation**
(lb/MMBtu, HHV)
NO
x
0.08 0.08
CO 0.04 0.06
VOC 0.004 0.006
PM-10 (front and back half) 0.01 0.02
* > 11.5% wet O
2
and Burner Inlet TEG Temperature > 850°F
** > 10.5% wet O
2
and Burner Inlet TEG Temperature > 750°F